Energy efficient operation strategy design for the combined cooling, heating and power system

dc.contributor.authorLiu, Mingxi
dc.contributor.supervisorShi, Yang
dc.date.accessioned2012-06-05T20:04:22Z
dc.date.available2012-06-05T20:04:22Z
dc.date.copyright2012en_US
dc.date.issued2012-06-05
dc.degree.departmentDepartment of Mechanical Engineering
dc.degree.levelMaster of Applied Science M.A.Sc.en_US
dc.description.abstractCombined cooling, heating and power (CCHP) systems are known as trigeneration systems, designed to provide electricity, cooling and heating simultaneously. The CCHP system has become a hot topic for its high system efficiency, high economic efficiency and less greenhouse gas (GHG) emissions in recent years. The efficiency of the CCHP system depends on the appropriate system configuration, operation strategy and facility size. Due to the inherent and inevitable energy waste of the traditional operation strategies, i.e., following the electric load (FEL) and following the thermal load (FTL), more efficient operation strategy should be designed. To achieve the highest system efficiency, facilities in the system should be sized to match with the corresponding operation strategy. In order to reduce the energy waste in traditional operation strategies and improve the system efficiency, two operation strategy design methods and sizing problems are studied (In Chapter 2 and Chapter 3). Most of the improved operation strategies in the literature are based on the ''balance'' plane, which implies the match of the electric demands and thermal demands. However, in more than 95% energy demand patterns, the demands cannot match with each other at this exact ''balance'' plane. To continuously use the ''balance'' concept, in Chapter 2, the system configuration is modified from the one with single absorption chiller to be the one with hybrid chillers and expand the ''balance'' plane to be a ''balance'' space by tuning the electric cooling to cool load ratio. With this new ''balance'' space, an operation strategy is designed and the power generation unit (PGU) capacity is optimized according to the proposed operation strategy to reduce the energy waste and improve the system efficiency. A case study is conducted to verify the feasibility and effectiveness of the proposed operation strategy. In Chapter 3, a more mathematical approach to schedule the energy input and power flow is proposed. By using the concept of energy hub, the CCHP system is modelled in a matrix form. As a result, the whole CCHP system is an input-output model. Setting the objective function to be a weighted summation of primary energy savings (PESs), hourly total cost savings (HTCs) and carbon dioxide emissions reduction (CDER), the optimization problem, constrained by equality and inequality constraints, is solved by the sequential quadratic programming (SQP). The PGU capacity is also sized under the proposed optimal operation strategy. In the case study, compared to FEL and FTL, the proposed optimal operation strategy saves more primary energy and annual total cost, and can be more environmental friendly. Finally, the conclusions of this thesis is summarized and some future work is discussed.en_US
dc.description.scholarlevelGraduateen_US
dc.identifier.bibliographicCitationM. Liu, Y. Shi, and F. Fang, "A new operation strategy for CCHP systems with hybrid chillers," Applied Energy, vol. 95, pp. 164-173, 2012.en_US
dc.identifier.bibliographicCitationM. Liu and Y. Shi, "An energy efficient optimal operation strategy design for CCHP systems," Canadian Society of Mechanical Engineers (CSME) International Congress, Winnipeg, Manitoba, Canada, June 4 - June 6, 2012.en_US
dc.identifier.bibliographicCitationH. Zhang, Y. Shi, and M. Liu, "H_{\infty} step tracking control for networked discrete-time nonlinear systems with integral and predictive actions," accepted with minor revisions, IEEE Transactions on Industrial Informatics, 2011.en_US
dc.identifier.urihttp://hdl.handle.net/1828/4002
dc.languageEnglisheng
dc.language.isoenen_US
dc.rights.tempAvailable to the World Wide Weben_US
dc.subjectCombined cooling, heating and power systemen_US
dc.subjectOperation strategyen_US
dc.subjectPower flowen_US
dc.subjectOptimizationen_US
dc.subjectBalance spaceen_US
dc.subjectPower generation unit sizingen_US
dc.subjectEnergy efficienten_US
dc.titleEnergy efficient operation strategy design for the combined cooling, heating and power systemen_US
dc.typeThesisen_US

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Liu_Mingxi_MASc_2012.pdf
Size:
11.72 MB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.74 KB
Format:
Item-specific license agreed upon to submission
Description: